Introduction
The YB□-12 Pre installed Substation arrives as one finished unit. The high-voltage switchgear, the transformer and the low-voltage panels are already installed and wired inside a single enclosure. You skip the civil work of a site-built substation, the footprint is small, and the unit can be moved to a new location later. It runs on 50Hz, 6–10kV networks and can feed a ring-main network or serve as the end point of a radial supply. An intelligent monitoring system can be added for remote "four-remote" control from a central station.
It sits in Gangheng's Transformer Substation range as the European-style option. Prefer a ground-mounted American layout? See the Pad Mounted Substation.
Units are built at our Jiangshan, Zhejiang base (5,000–20,000 m²). Steel is cut on laser cutters and CNC punching machines, formed on CNC bending machines, and copper busbars are shaped on a dedicated bending machine. Finished units go through in-house testing.
Model Code Explained
-

YB = pre installed (prefabricated) substation | □ = design serial number | 12 = HV rated voltage (kV) | /□ = transformer rated capacity (kVA)
Layouts and Wiring Schemes
Each YB□-12 is assembled from modules, so you configure it by choosing four things.
| Choice | Options |
| HV network connection | Ring-main type; terminal type |
| Room layout | "目" in-line layout; "品" triangular layout (two variants each) |
| Transformer | Fully sealed oil-immersed; dry-type |
| Enclosure | Metal shell; non-metal shell |
| HV load switch | Compressed-air, vacuum or SF6 type |
You also pick a wiring scheme: 7 HV main-circuit schemes, 7 LV main-circuit schemes, and typical HV + LV combinations.
Technical Parameters
Product factory real shot



Basic Electrical Parameters
|
Parameter |
Value |
|
Rated Voltage (HV side) |
12kV |
|
Rated Voltage (LV side) |
0.4kV |
|
Auxiliary Circuit Voltage |
AC 110V, 220V, 380V; DC 24V, 220V |
|
Transformer Rated Capacity |
50, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600 kVA |
|
Rated Current (HV) |
400A, 600A |
|
Rated Current (LV) |
100A–2500A |
|
Rated Frequency |
50Hz (60Hz available) |
Withstand Current & Insulation Levels
|
Parameter |
Value |
|
HV Short-Time Withstand Current (12kV) |
16kA/2s (4s); 20kA/2s (4s) |
|
LV Short-Time Withstand Current |
250–315kVA: 15kA; 400–800kVA: 30kA; 1000kVA and above: per actual short-circuit current (200kVA and below: exempt from test) |
|
HV Peak Withstand Current (12kV) |
40kA, 50kA |
|
LV Peak Withstand Current |
250–315kVA: 30kA; 400–800kVA: 63kA; 1000kVA and above: 2.2× short-time withstand current (200kVA and below: exempt from test) |
|
Rated Short-Circuit Making Current (12kV) |
40kA, 50kA |
|
HV Lightning Impulse Withstand (12kV): phase-to-earth & phase-to-phase / isolating distance |
75kV / 85kV |
|
HV 1-min Power-Frequency Withstand (12kV): phase-to-earth & phase-to-phase / isolating distance |
42kV / 48kV |
|
LV 1-min Power-Frequency Withstand |
60≤Ui≤300: 2000V; 300≤Ui≤660: 2500V |
|
Transformer Power-Frequency Withstand (1 min, 7.2kV / 12kV; dry-type in brackets) |
25 (20)kV / 35 (28)kV |
|
Transformer Impulse Withstand Peak (1.2/50µs, 7.2kV / 12kV) |
60kV / 75kV |
|
Rated Noise Level |
Oil-immersed transformer: ≤50dB; dry-type transformer: ≤55dB |
|
Reactive Power Compensation |
30% of transformer capacity by default; adjustable on request |
Overall Dimensions
|
Layout |
Length |
Width |
Height |
|
"目" in-line layout |
2900–4500 mm |
1910–2450 mm |
2360–3680 mm |
|
"品" triangular layout |
1810–2450 mm |
1500–2300 mm |
2380–3680 mm |
Exact dimensions depend on the capacity and wiring scheme you choose. Contact us for the size of your configuration.
Built-In Design Details
- Common base frame. Channel steel and I-beam are welded into one base. The HV and LV equipment frames and the transformer housing are bonded to it by grounding conductors. Earthing terminals at the four corners let you pick the grounding point from any direction.
- Transformer room cooling. A double-layer metal roof and internal insulation limit heat gain. An automatic exhaust fan is started and stopped by the room's temperature monitoring device.
- Safer access. The transformer room has doors on both sides. Behind each door sits an isolation net, with an interlock alarm to keep people out of live compartments.
Foundation and Installation

Pour a concrete pier or build a brick foundation with a 20 mm cement-mortar finish on top, set on compacted ground.
Foundation length = A + 1500mm
Foundation width = B + 1000mm
A and B are the enclosure's length and width. Precast footing slabs and perforated support plates are part of the foundation drawing. Place at least two grounding rods near the anchor bolts. Dimensions A, B and C depend on the scheme you choose, so confirm them with us at ordering.
Environmental Operating Conditions
| Parameter | Value |
| Altitude | ≤1000m |
| Ambient Temperature | -25°C to +40°C |
| Seismic Intensity | ≤8 degree |
| Outdoor Wind Speed | ≤35m/s |
| Site Requirements | Not suitable for sites with fire or explosion hazards, heavy pollution, chemical corrosion or intense vibration. If your site is outside these conditions, contact us. |
Customization
How a custom YB□-12 order works:
- Send your transformer rating and site drawing. We match a layout and wiring scheme to them.
- No technical data yet? Describe the site, the connected equipment loads and the functions you need. Our engineers work out the scheme from that.
- Cost. Most custom builds cost the same as the standard unit. The usual exception is a wider enclosure.
- Colour. Send a colour card and we finish the shell to match.
- Quantity. Orders start at one unit.

Applications
Where a pre installed substation fits best:
| Site | Why it works |
| High-rise buildings, residential districts | Small footprint close to the load |
| Factories and mines | Quick to set up near production areas |
| Hotels, shopping centers, parks | Neat enclosure for public areas |
| Oilfields, airports, ports and docks, railways | Outdoor supply points |
| Temporary facilities | Movable, short production cycle |
| Power systems (generation, transmission, distribution) | Terminal or ring-main supply |
Certifications
Gangheng is a qualified supplier to State Grid and China Southern Power Grid, and our products are listed on the State Grid e-commerce procurement platform.

- ISO9001 quality management
- ISO14001 environmental management
- OHSAS18001 occupational health and safety
- CCC certification
- Type test report available on request

Project Case
Guoneng Shendong Coal Group
China · Coal mine · 2020
Box-type substation supplied for a mining area.

Manufacturing & Quality Control
-

Production Base: Jiangshan, Zhejiang, in the transport hub where Zhejiang, Fujian, Jiangxi and Anhui meet. The base is under 3 km from the Quzhou South exit of the G3 expressway and under 7 km from Jiangshan railway station. National Road 205 and the Zhejiang–Jiangxi railway pass nearby.
-

Key Equipment: laser cutting for steel sheet, CNC punching and CNC bending for the enclosure, a dedicated copper busbar bending machine, and testing equipment for the finished unit.
-

Company Scale: 50–200 employees; 5,000–20,000 m² facility; annual revenue RMB 50–100 million; 5 utility model patents
Experience: making power distribution equipment since 2004
Delivery & Trade Terms
| Term | Detail |
| Minimum order | 1 unit |
| Lead time | From 30 days; the schedule lengthens as order volume grows |
| Condition | New, unused equipment only |
Warranty & After-Sales Service
| Stage | Coverage |
|---|---|
| Installation and commissioning | Quality inspection; defects and missing parts handled promptly |
| Months 1–12 after acceptance | Free warranty |
| After the warranty ends | 5 years of hidden-defect protection |
| Throughout | 24/7 on-site support; spare parts at or below market price; technical documents and training |
Frequently Asked Questions
Q: Which transformer ratings can I choose for the YB□-12 pre installed substation?
A: Fourteen ratings from 50 to 1600 kVA: 50, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250 and 1600. The HV side is 12kV and the LV side 0.4kV.
Q: Oil-immersed or dry-type transformer?
A: Either. Oil-immersed units are rated ≤50dB and dry-type units ≤55dB.
Q: Can the YB□-12 be customized?
A: Yes. Send transformer capacity and drawings, or site details and loads. See the customization steps above.
Q: What operating conditions is it built for?
A: Altitude up to 1000m, -25°C to +40°C, seismic intensity up to 8 degrees and outdoor wind up to 35m/s. Contact us if your site is outside these limits.
Q: Is a 60Hz version available?
A: Yes. 50Hz is standard and 60Hz is available.
Q: What do I send to start an order?
A: The model, transformer type and capacity, HV/LV wiring scheme with component types and parameters, shell colour, and any other requirements. Without technical documents, our engineers can work from your site information.
Q: How fast can I get one?
A: The base lead time is 30 days. Larger orders take longer.
Q: What happens after the warranty?
A: Free warranty runs 12 months from acceptance. Hidden-defect protection continues for 5 years after that.
Ready to specify your pre installed substation? Send us your site details and request a quote.