Introduction
An oil immersed combined distribution transformer puts the transformer, the high-voltage load switch and the high-voltage fuse into one factory-assembled unit. The switch and fuse sit inside the transformer's oil tank. For buyers and EPC contractors, this means one compact, pre-assembled unit that steps 6–10 kV grid power down to 0.4 kV, so there is no separate switchgear room to build. It is widely used in urban and rural distribution networks.
The ZGS(YB)□-12 is the American-style (pad-mounted) model in Gangheng's Transformer Substation range. It is our first-generation domestically developed American-style substation. For other layouts in the same family, see our Pad Mounted Substation.
Every unit is built at Gangheng's production base in Jiangshan, Zhejiang, with CNC punching machines, CNC bending machines, laser cutting machines and copper busbar bending machines, and is tested in-house before shipment.
How the Combined Structure Works
- Load switch and fuse inside the oil tank. They share the tank with the transformer body, so the live parts are fully enclosed and insulated.
- Bayonet-type fuse. The fuse is the plug-in type. A blown fuse does not affect the quality of the transformer oil. A back-up current-limiting fuse is also fitted.
- Fully sealed oil tank. The tank carries an oil temperature gauge, oil level gauge, pressure gauge, pressure relief valve and oil drain valve to monitor the transformer's operating condition.
- Three enclosure styles. Standard, reinforced and composite, chosen according to how complex the low-voltage outgoing requirements are.
- Ring-main or terminal supply. The high-voltage wiring can be used in a ring main or as a terminal. A metering device can be added at the terminal end.




Technical Parameters
The tables below give the key data of the ZGS(YB)□-12 oil immersed combined distribution transformer. Standard units follow GB/T; ANSI/IEEE (US) and BS (UK) standards can be applied on request. Figures in brackets are for the isolating (open-contact) gap.
HV Load Switch
|
Rated Current (A) |
Rated Voltage (kV) |
Lightning Impulse Withstand (kV) |
Power-Frequency Withstand (kV) |
Thermal Stability Current (kA/s) |
Dynamic Stability Current (kA) |
Short-Circuit Making Current (kA) |
Load Operations |
Mechanical Operations |
|
400 |
12 |
75 (85) |
42 (48) |
12.5 / 2 |
31.5 |
31.5 |
100 |
2000 |
|
630 |
12 |
75 (85) |
42 (48) |
16 / 4 |
40 |
40 |
100 |
3000 |
Transformer
|
Item |
Specification |
|
Rated Capacity |
80–1600 kVA |
|
Voltage Combination |
HV 6 / 6.3 / 10 kV; LV 0.4 kV (10 kV is the most common; other voltages per customer requirement) |
|
Tap Changer |
Off-circuit, ±5% / ±2.5% |
|
Connection Group |
Yyn0 / Dyn11 |
|
Core |
Stacked silicon-steel, wound core or amorphous alloy |
|
Winding |
Copper, aluminum or both |
|
Tank |
Flat panel with radiator fins |
|
Noise |
45 dB |
|
Temperature Rise |
Top oil 50 K; winding 65 K |
|
Protection Degree |
IP33 (complete unit) |
|
Enclosure |
Cold-rolled steel plate, powder-coated; stainless steel available for coastal / high-salt-spray sites |
|
Frequency |
50 Hz |
|
Applicable Standards |
GB/T by default; ANSI/IEEE (US) and BS (UK) on request |
Operating Conditions
|
Condition |
Specification |
|
Ambient Temperature |
−30°C to +45°C |
|
Altitude |
≤1000 m |
|
Seismic Intensity |
≤8 |
|
Outdoor Wind Speed |
≤35 m/s |
|
Site |
No fire or explosion hazard, heavy pollution, chemical corrosion or severe vibration |
If the site does not meet these conditions, please consult us before ordering.
No-Load / Load Performance by Capacity
|
Capacity (kVA) |
No-Load Loss (kW) |
Load Loss (kW) |
No-Load Current (%) |
|
80 |
0.19 |
1.10 |
1.1 |
|
100 |
0.22 |
1.30 |
1.0 |
|
160 |
0.31 |
1.85 |
0.8 |
|
200 |
0.32 |
2.25 |
0.7 |
|
250 |
0.45 |
2.65 |
0.7 |
|
315 |
0.54 |
3.05 |
0.6 |
|
400 |
0.65 |
3.80 |
0.6 |
|
500 |
0.75 |
4.50 |
0.5 |
|
630 |
0.91 |
5.30 |
0.5 |
|
800 |
1.08 |
6.80 |
0.5 |
|
1000 |
1.26 |
8.10 |
0.4 |
|
1250 |
1.54 |
9.50 |
0.4 |
|
1600 |
1.86 |
11.40 |
0.4 |
Overall Dimensions
Standard-form outline dimensions in mm (reference only). Three enclosure forms are available: standard, reinforced and composite. Choose according to how complex your LV outgoing arrangement is; we confirm the form with you.
|
kVA |
A |
B |
C |
D |
E |
H |
|
100–250 |
1840 |
1780 |
1250 |
705 |
555 |
1400 |
|
315–400 |
1840 |
1780 |
1450 |
705 |
555 |
1500 |
|
500–630 |
1840 |
1780 |
1550 |
705 |
625 |
1500 |
|
800–1000 |
2000 |
1780 |
1700 |
705 |
765 |
1500 |
|
1250 |
2200 |
1780 |
2000 |
705 |
855 |
1550 |
For 80 kVA and 1600 kVA outline dimensions, please contact us.

Installation and Foundation
The brochure includes a reference foundation drawing, marked for reference only. The quantity and position of HV and LV outgoing conduits are decided by the user. For project work, confirm the formal foundation drawing and cable entry positions with our engineers.
Main Circuit Schemes
Like switchgear, this unit is selected as a combination of schemes, so you can match it to the supply and load on site.
High-voltage primary schemes (FYN-12 load switch, 315–630 A)
|
No. |
Scheme |
Use |
|
I |
Terminal supply |
Single incoming feeder |
|
II |
Dual power supply |
Two incoming sources |
|
III |
Ring main + dual power supply |
Ring-network loops |
|
IV |
HV metering scheme |
Metering at the HV side |
Low-voltage main schemes (8 options)
|
Scheme |
Main Switch |
Branch Switches |
Metering |
Reactive Compensation |
|
1 |
- |
100–630 A |
- |
- |
|
2 |
630–1600 A |
100–630 A |
- |
- |
|
3 |
- |
100–630 A |
kWh / kVarh |
- |
|
4 |
630–1600 A |
100–630 A |
kWh / kVarh |
- |
|
5 |
- |
100–630 A |
- |
30–300 kVar |
|
6 |
630–1250 A |
100–630 A |
- |
30–300 kVar |
|
7 |
- |
100–630 A |
kWh / kVarh |
30–300 kVar |
|
8 |
630–1250 A |
100–630 A |
kWh / kVarh |
30–300 kVar |
Reactive compensation can be automatic switching or fixed. LV breakers can be frame-type or molded-case circuit breakers.
-

Single-Line Diagram
HV schemes I–IV combine with LV schemes 1–8 to form a complete substation configuration. Tell us your supply mode and LV circuits, and we confirm the combination with you.
-

Customization and Ordering
We support custom configurations. Provide the transformer capacity and the site drawings, and we design a matching scheme. If you do not have these figures, tell us the site, the load of the equipment on it and the function you need, and our engineers will propose a scheme from that.
You can customize: number of low-voltage outgoing circuits, metering, reactive power compensation, enclosure size, color, nameplate and language, and eco-friendly oil (consistent with the transformer oil).
To start, please provide: transformer capacity, supply mode (terminal or ring main), number of LV circuits and their currents, ambient temperature and altitude, applicable standard, metering requirements and compensation capacity.
To order, also provide the transformer model and capacity, HV and LV main wiring diagrams, special component specifications, enclosure color (if none is specified, the manufacturer decides) and spare parts. Customized units are, in most cases, priced the same as the standard configuration (the cabinet width may increase). There is no minimum order quantity; a single unit can be delivered.
-

Site Conditions
Cold sites: down to −30°C
Warm sites: up to +45°C
Windy sites: outdoor wind up to 35 m/s
Low-altitude sites: up to 1000 m
Coastal / high-salt-spray sites: anti-corrosion treatment available, with a stainless-steel enclosure
Applications
|
Industry |
Description |
|
Power Systems |
Generation, transmission and distribution |
|
Power Plants & Substations |
Supporting power supply for plants and substations |
|
Petrochemical |
Distribution for petrochemical sites |
|
Metallurgy & Steel |
Distribution for metallurgical and steel sites |
|
Light Industry & Textile |
Distribution for light-industry and textile plants |
|
Factories & Mines |
Compact power supply on factory and mine sites, for example the Xianglong Coal Mine project |
|
Residential Areas & High-Rise Buildings |
Distribution for residential areas and high-rise buildings |
Quality Certification
- Listed on the State Grid e-commerce procurement platform. Qualified supplier to State Grid and China Southern Power Grid. Gangheng is also a National High-Tech Enterprise.
- ISO 9001 (Quality Management System)
- ISO 14001 (Environmental Management System)
- OHSAS 18001 (Occupational Health and Safety Management System)
- CCC certification
- Type test report
- Factory tests on every unit: winding resistance, ratio, no-load loss, power-frequency withstand and sealing test.
- Patents: 5 utility-model patents.
-

Manufacturing and Quality Control
23 years in power distribution equipment (founded in 2004). The Jiangshan plant is less than 3 km from the Quzhou South exit of the G3 Beijing–Taipei Expressway and less than 7 km from Jiangshan railway station, with National Highway 205 and the Zhejiang–Jiangxi railway nearby.
Key equipment: CNC punching machines, CNC bending machines, laser cutting machines, copper busbar bending machines and testing equipment.
Scale: 50–200 employees; 5,000–20,000 m² site; annual revenue RMB 50–100 million.
Project Case
|
Customer |
Product |
Details |
|
Xianglong Coal Mine, China |
American-style substation |
Supplied in 2016 for a mine site |
Other Gangheng references: custom KYN28-12 switchgear for Shangrao Jizhi (accepted), and fixed-type switchgear for Zhejiang Wangpai Home, supplied steadily since 2015.
Delivery and Trade Terms
No MOQ. Single-unit orders are accepted.
Lead time depends on order value: about 30 days for a USD 300,000 order, 45 days for USD 700,000 and 60 days for USD 1,500,000. A standard-configuration single unit or small batch takes 15–30 days.
Packaging: bare unit with protection. The transformer is filled with oil at the factory.
Documents shipped with the unit: basic and installation drawings, manual, factory test report, certificate of conformity.
All equipment supplied is brand new and unused.
Warranty and After-Sales Service
12 months free warranty after acceptance.
Hidden-defect protection for 5 years after the warranty ends.
24/7 on-site support; spare parts priced no higher than the market.
Technical documents and training.
Defects and missing parts handled promptly during installation and commissioning, with quality inspection.
Video guidance for installation is available.
Frequently Asked Questions
Q: What voltage and capacity does the ZGS(YB)□-12 oil immersed combined distribution transformer cover?
A: It is a 12 kV unit with HV of 6, 6.3 or 10 kV and 0.4 kV LV. The capacity is 80–1600 kVA, and the load switch is rated 400 A or 630 A.
Q: Can the unit be customized to my transformer or site data?
A: Yes. Give us the transformer capacity and drawings, or the site equipment load and the function you need, and we design the scheme. Customization is, in most cases, priced the same as standard (the width may increase).
Q: Which standards does it meet? Can it meet ANSI/IEEE or BS?
A: Standard units follow GB/T. ANSI/IEEE (US) and BS (UK) standards can be applied on request.
Q: Is there a minimum order quantity?
A: No. A single unit can be delivered.
Q: What is the lead time?
A: A standard-configuration single unit or small batch takes 15–30 days. Larger orders: about 30 days for a USD 300,000 order, 45 days for USD 700,000 and 60 days for USD 1,500,000.
Q: What does the warranty cover, and what happens after it ends?
A: The warranty is 12 months of free repair after acceptance. After that, we remain responsible for hidden defects for 5 years. We also provide 24/7 on-site support.
Q: Is the transformer oil included? How is the unit shipped?
A: The oil is filled at the factory. The unit ships bare with protective packaging, together with its drawings, manual, factory test report and certificate.
Q: Can you provide drawings and technical data before I order?
A: Yes. Send your requirements and we provide the scheme drawings and technical data. To order, please also provide the transformer model and capacity, the HV and LV main wiring diagrams, special component parameters, the enclosure color and spare-part requirements.
Hot Tags: oil immersed combined distribution transformer, China oil immersed combined distribution transformer manufacturers, suppliers, factory, compact transformer substation, fully enclosed substation, package transformer substation, pad mounted substation, Pad Mounted Transformer, prefab substation