KYN28A Scheme Selection Guide

KYN28A-12(Z) High Voltage Switchgear – Circuit Scheme Selection Guide

 

GangHeng's KYN28A-12(Z) armoured withdrawable AC metal-clad switchgear is designed for 3–10kV three-phase, 50Hz single-busbar systems in power plants, substations, mines, industrial parks and high-rise buildings. It receives and distributes electrical power while providing control, protection and monitoring for the circuit. The withdrawable (truck-type) design lets the circuit breaker be racked out as a complete unit for maintenance - offering clearer, more reliable isolation than fixed-mounted switchgear such as KYN61 or XGN series.

 

This guide helps you quickly identify the right KYN28A-12(Z) configuration based on cabinet role, rated current/breaking capacity, and operating mechanism. Beyond the standard scheme library, GangHeng also offers custom configurations at the same price as standard products.

Complies with GB3906 AC Metal-Enclosed Switchgear and Controlgear for Rated Voltages 3.6kV to 40.5kV, and GB/T11022 Common Specifications for High-Voltage Switchgear and Controlgear Standards.

 

 

Model Designation

Code Position Meaning
K Withdrawable (truck) type
N Indoor
28A Design series number
12 Rated voltage class (12kV)
(Z) Vacuum circuit breaker
page-566-378

 

 

 

 

1. How to Select

 

Product drawing

page-1200-1800
page-1200-1800
page-1200-1800

 

 

 

Step 1 – Determine the Cabinet's Functional Role

 

Role

Description

Incoming Cabinet

Overhead or cable incoming, bringing utility/transformer power into the distribution system - the first point of the switchgear lineup

Feeder / Outgoing Cabinet

Distributes power to downstream loads; positioned at the end of the cabinet lineup

Bus-tie Cabinet

Dual-power switching or bus-section tie-in, improving supply reliability

PT Cabinet (Voltage Metering)

Voltage measurement, can be combined with reactive power compensation

Metering Cabinet

Dedicated to energy metering circuits

Isolation Cabinet

Electrically isolates adjacent cabinet groups

Capacitor Cabinet

Houses high-voltage capacitors for reactive power compensation

Transformer (Auxiliary) Cabinet

Houses the station service / auxiliary transformer

 

These roles can be configured individually or combined (e.g. "Incoming + Bus-tie", "Bus-tie + Feeder + Standby") - see the scheme library and combination examples below.

 

 

Step 2 – Determine Current Rating Based on Transformer Capacity

 


 

page-1200-800

Rated voltage: 3.6kV / 7.2kV / 12kV. Rated current: 630A up to 3150A. Cabinet width is linked to the busbar current rating: 800mm width for branch busbar current up to 1250A; 1000mm width for 1600A and above (thermal stability 40kA).

The exact current rating and breaking capacity should be confirmed by an engineer based on actual transformer capacity and load calculations. If you can provide your transformer capacity, our engineering team will match the precise cabinet type and current step for you.

 

 

Step 2 – Determine Current Rating Based on Transformer Capacity


 

page-1200-675

• Circuit breaker operating mechanism: manual, motor-operated, or spring-stored energy - configurable

• Truck (withdrawable) operation: the breaker truck moves between the service and test positions via a manual crank handle (counter-clockwise to withdraw, clockwise to rack in); a dedicated transfer carriage is used only for moving the truck outside the cabinet

• Current transformers (CT) and voltage transformers (PT): selectable ratios, customer-specified ratios supported

• Five-anti ("five-prevention") interlocking system: prevents mis-operation of the breaker, prevents racking the truck in/out on load, prevents closing onto an earthed circuit, prevents energizing with the earthing switch closed, and prevents unauthorized access to a live compartment

 

 

Step 4 – Review Reference Schemes Under the Matching Category

 

 

 

Each cabinet role has multiple standard circuit schemes available - see the categorized library below, or consult the full scheme library for the complete set.

 

 

2. Circuit Scheme Library by Function

 

The KYN28A-12(Z) series includes 80 standard main-circuit schemes. Key components include the vacuum circuit breaker (ZN63A / VD4), current transformers, voltage transformers, earthing switches and fuses, with quantities configured per scheme. Cabinet width is 800mm, or 1000mm where rated current is 1600A and above; some overhead-line and metering schemes use a 1660mm cabinet depth.

page-1200-675

 

 

Category 1: Incoming Cabinet

 

Brings power into the distribution system via overhead or cable incoming lines. Can be configured standalone, or combined with bus-tie functions for dual-power supply. Typically fitted with circuit breakers, current transformers and, where required, voltage transformers for metering.

 

page-924-579
page-918-567
page-927-579

Scheme 01–06, 19–28, 33–40 | Single / Dual Incoming Supply, with optional PT | Width 800–1000mm, Depth 1500–1660mm | For single- or dual-source power entry, overhead or cable

 

 

 

Category 2: Feeder / Outgoing Cabinet

 

Distributes power to downstream loads via overhead or cable outgoing lines, optionally combined with voltage metering (PT) or power factor correction.

page-930-578
page-927-579

Scheme 02, 03, 05, 29–32 | Outgoing Feeder, with optional PT | Width 800–1000mm, Depth 1500mm | For distributing power to downstream loads with cable or overhead outgoing lines

 

Category 3: Bus-tie Cabinet

 

Used for bus-section tie-in or dual-power switching. Can be configured standalone, or combined with feeder functions for improved system reliability.

 

page-918-582
page-924-573

Scheme 07–18, 49–52 | Bus-tie (left/right) / Bus Coupler | Width 800–1000mm, Depth 1500mm | For basic bus-section/dual-power switching

 

 

 

Category 4: PT (Voltage Metering) Cabinet

 

 Dedicated to voltage measurement, optionally combined with surge arresters or bus-tie functions.

 

page-921-579
page-924-576

Scheme 41–48 | Voltage Metering, with optional Arrester / Bus-tie | Width 800–1000mm, Depth 1500mm | For accurate voltage measurement and protection

 

 

Category 5: Metering Cabinet

 

Dedicated energy-metering circuits, optionally combined with left/right bus-tie or cable incoming. 

page-935-585
page-927-579
page-924-576
page-921-570

Scheme 61–76 | Metering, with optional Bus-tie / Cable Incoming | Width 800–1000mm, Depth 1500–1660mm | For accurate energy metering integrated with adjacent cabinet functions

 

 

Category 6: Isolation Cabinet

 

Provides electrical isolation between cabinet groups, optionally combined with bus-tie or voltage metering.

 

page-921-576
page-918-576

Scheme 53–60 | Isolation, with optional Bus-tie / Voltage Metering | Width 800–1000mm, Depth 1500mm | For sectional isolation between cabinet groups

 

 

Category 7: Capacitor & Auxiliary Transformer Cabinet

 

High-voltage capacitor banks for reactive power (power factor) compensation, and a dedicated cabinet for the station-service (auxiliary) transformer. 

 

page-929-579

Scheme 77 | High-Voltage Capacitor Bank | Width 800–1000mm | Power factor correction

Scheme 78 | Auxiliary/Station-Service Transformer | Width 800–1000mm, Depth 1660mm when transformer capacity exceeds 50kVA | Houses the switchgear's own auxiliary transformer

 

The schemes above are representative examples. The full KYN28A-12(Z) series includes 80 standard circuit schemes, plus typical multi-cabinet combination examples (e.g. dual-bus incoming + bus-tie + metering + feeder). View Full Scheme Library →

 

 

 

 

 
Technical Parameters

Item

Unit

Data

Rated voltage

kV

3.6, 7.2, 12

Rated frequency

Hz

50

Rated current of circuit breaker

A

630, 1250, 1600, 2000, 2500, 3150

Rated current of switchgear

A

630, 1250, 1600, 2000, 2500, 3150

Rated short-time withstand current (4s)

kA

16, 20, 25, 31.5, 40

Rated peak withstand current

kA

40, 50, 63, 80, 100

Rated short-circuit breaking current

kA

16, 20, 25, 31.5, 40

Rated short-circuit making current (peak)

kA

40, 50, 63, 80, 100

1min power-frequency withstand voltage - phase-phase/earth

kV

24, 32, 42

1min power-frequency withstand voltage - across isolating distance

kV

24, 32, 48

Rated lightning impulse withstand voltage (peak) - phase-phase/earth

kV

40, 60, 75

Rated lightning impulse withstand voltage (peak) - across isolating distance

kV

46, 70, 85

Degree of protection

-

IP4X for the enclosure; IP2X when compartment/breaker doors are open

 

 

Operating Conditions

 

Ambient air temperature: -15°C to +40°C, 24-hour average not exceeding +35°C

• Altitude: ≤1000m for 10kV systems; ≤3000m for 6kV systems

• Relative humidity: daily average ≤95% (daily average water vapor pressure ≤2.2kPa); monthly average ≤90% (monthly average water vapor pressure ≤1.8kPa)

• Seismic intensity ≤ 8 degrees

• Ambient air free from significant pollution by corrosive gases, flammable gases, water vapor or salt fog

• No severe pollution or frequent, intense vibration

Note: if site conditions exceed the above specifications, please consult GangHeng's engineering team.

page-900-675

 

Structural Features
 
 

1. Modular, fully metal-clad construction - assembled from a modular metal-clad frame for consistent quality and easy expansion.

2. High-precision cabinet frame - made from imported aluminum-zinc coated steel sheet, CNC-machined with advanced multi-fold bending and joined with riveted nuts and high-strength bolts; corrosion resistant, lightweight, high strength, strong interchangeability.

page-1200-675
 

3. Compatible circuit breakers - fits GangHeng's own ZN63A-12 (VS1) series or imported VD4 series vacuum circuit breakers; wide applicability, high reliability, maintenance-free.

4. Dedicated service/test positions - the breaker truck has clearly indicated service and test positions for safe, reliable operation.

Full truck interchangeability - trucks of the same rating can be freely swapped between cabinets.

page-1200-675

 

 

5. Dedicated transfer carriage - moves the truck between cabinets for light, flexible handling.

6. High cable capacity - cable compartment accommodates up to 9 single-core cables.

7. "Five-anti" interlocking - reliable mechanical and electrical interlocks fully satisfy five-prevention (five-anti) safety requirements.

8. Pressure-relief protection - pressure-relief channels in the high-voltage compartments protect personnel safety.

page-1200-675

 

 

9. Front viewing windows - allow observation of internal component status without opening the door.

10. Front-access maintenance - serviceable from the front, suitable for wall-mounted installation.

11. Insulated compartment barriers - fitted with live-status indication devices between compartments.

12. Custom enclosure finish - polyester powder coating, standard color grey; custom colors available on request (color sample required).

page-513-504

KYN28A switchgear structural diagram: A Busbar compartment B Breaker truck compartment C Cable compartment D

Relay/instrument compartment:

1 Pressure relief device 2 Enclosure 3 Branch busbar 4 Busbar bushing 5 Main busbar 6 Static contact assembly 7 Static contact box

8 Current transformer 9 Earthing switch 10 Cable 11 Surge arrester 12 Earthing busbar 13 Removable partition 14 Shutter (partition)

15 Secondary plug 16 Breaker truck 17 Heater/dehumidifier 18 Withdrawable partition 19 Earthing switch operating mechanism

20 Control wiring duct 21 Base frame

 

 

Overall & Installation Dimensions

Item

Configuration

Value

Height C (mm)

-

2300

Width A (mm)

Branch busbar rated current up to 1250A

800

Width A (mm)

Branch busbar rated current 1600A and above, 40kA thermal stability

1000

Depth B (mm)

Cable incoming/outgoing

1500

Depth B (mm)

Overhead incoming/outgoing

1660

Weight (kg)

-

700–1200

KYN28A switchgear overall dimensions
 

 

Installation Base Dimensions

 

 

Cabinet Width A

Cabinet Depth B

L1

L2

L3

800

1500 (cable)

800

530

630

800

1660 (overhead)

800

530

630

1000

1500 (cable)

1000

730

830

1000

1660 (overhead)

1000

730

830

KYN28A switchgear installation base dimensions

 

 

Custom Circuit Scheme Configuration

 

Beyond the standard scheme library, GangHeng offers custom KYN28A-12(Z) configurations, including: widened cabinets, special busbar arrangements, and special secondary circuits.

page-1200-800
 

Path A – With Technical Parameters

Customer provides transformer capacity, system drawings and other parameters; GangHeng's engineering team delivers a custom scheme directly.

 

Path B – Without Technical Parameters

Customer provides site information, on-site equipment power ratings, and the desired functional outcome; GangHeng's engineering team derives and delivers a custom scheme accordingly.

page-1200-800

 

Notes:

• Custom configurations are priced the same as standard schemes; final cost may vary depending on the specific customization
• Cabinet dimensions may be widened depending on the specific configuration
• No minimum order quantity
• Standard lead time is approximately 30 working days for typical orders; larger or highly customized orders are scheduled case by case
• GangHeng brings 23 years of industry experience, is a qualified supplier for State Grid and China Southern Power Grid, and holds ISO9001 and CCC certifications

 

 

Ordering Information
 

 

 

When placing an order, customers should provide:

 

  • Main circuit scheme number, main circuit system diagram, cabinet arrangement drawing, and layout plan
  • Auxiliary/control circuit wiring diagram and terminal block layout
  • Model, specification and quantity of in-cabinet components
  • Where busbar bridges are required (between cabinet rows or through walls), please provide span and ground clearance dimensions
  • Enclosure color (standard color is grey unless otherwise specified)
  • Any special site conditions or other requirements outside standard operating conditions
news-1800-1200

 

If this technical documentation is not available, please refer to Custom Path B above - GangHeng's engineering team will assist in developing the scheme.

 

 

Frequently Asked Questions

 

Q: What are incoming, feeder, bus-tie, PT, metering, isolation and capacitor cabinets used for?

A: Incoming cabinets bring power (utility or transformer) into the distribution system. Feeder cabinets distribute power downstream. Bus-tie cabinets handle dual-power switching or bus-sectioning. PT cabinets measure voltage, metering cabinets measure energy consumption, isolation cabinets separate cabinet groups electrically, and capacitor cabinets provide reactive power compensation. All can be used standalone or combined.

Q: How do I know which current/breaking-capacity rating to choose?

A: This depends on your actual site conditions - transformer capacity, load calculation and system short-circuit capacity. We recommend providing your transformer capacity so our engineers can confirm the exact match.

Q: What is the difference between KYN28 and other high-voltage switchgear types such as KYN61 or the XGN series?

A: KYN28 is rated at 10kV (12kV class) and uses a withdrawable (truck-type) construction. KYN61 is rated at 35kV. KYN61 and the XGN series are typically fixed-mounted designs (the circuit breaker is permanently installed). A withdrawable design is more advanced and safer, with a clearer, more positive isolating break than a fixed-mounted breaker.

Q: What are the advantages of withdrawable (truck-type) switchgear compared with fixed-mounted types?

A: In a fixed-mounted design the breaker cannot be removed, so maintenance carries higher exposure risk. With KYN28's withdrawable truck, the breaker can be racked out completely to the test/maintenance position, giving a more thorough and visible isolation and a higher level of safety.

Q: Is SF6-free / environmentally friendly configuration supported?

A: Yes.

Q: Do you provide installation and commissioning support?

A: Yes - remote video-guided installation support is available, in addition to 24/7 on-site support.

Q: Does a custom scheme cost more or take longer?

A: Pricing depends on the specific customization requested. Standard lead time is approximately 30 working days; larger or highly customized orders are scheduled case by case.

Q: Is there a minimum order quantity (MOQ)?

A: No minimum order quantity - a single unit can be supplied.

Q: Where can I see all 80 standard schemes?

A: Click "View Full Scheme Library" on this page, or contact our engineering team, to access the complete KYN28A-12(Z) main circuit scheme manual with all standard scheme numbers and configuration details.

 

 

Request a Technical Proposal

Please provide the following information, and GangHeng's engineering team will match or customize a KYN28A-12(Z) circuit scheme for you:

If technical parameters are available:

  • Transformer capacity
  • System voltage level
  • Related drawings (main circuit system diagram, layout plan, etc.)
page-1000-667

If technical parameters are not available

  • Site information
  • On-site equipment power ratings
  • Desired distribution function

 

 

 