KYN28A-12(Z) High Voltage Switchgear – Circuit Scheme Selection Guide
GangHeng's KYN28A-12(Z) armoured withdrawable AC metal-clad switchgear is designed for 3–10kV three-phase, 50Hz single-busbar systems in power plants, substations, mines, industrial parks and high-rise buildings. It receives and distributes electrical power while providing control, protection and monitoring for the circuit. The withdrawable (truck-type) design lets the circuit breaker be racked out as a complete unit for maintenance - offering clearer, more reliable isolation than fixed-mounted switchgear such as KYN61 or XGN series.
This guide helps you quickly identify the right KYN28A-12(Z) configuration based on cabinet role, rated current/breaking capacity, and operating mechanism. Beyond the standard scheme library, GangHeng also offers custom configurations at the same price as standard products.
Complies with GB3906 AC Metal-Enclosed Switchgear and Controlgear for Rated Voltages 3.6kV to 40.5kV, and GB/T11022 Common Specifications for High-Voltage Switchgear and Controlgear Standards.
Model Designation
| Code Position | Meaning |
| K | Withdrawable (truck) type |
| N | Indoor |
| 28A | Design series number |
| 12 | Rated voltage class (12kV) |
| (Z) | Vacuum circuit breaker |

1. How to Select
Product drawing



Step 1 – Determine the Cabinet's Functional Role
|
Role |
Description |
|
Incoming Cabinet |
Overhead or cable incoming, bringing utility/transformer power into the distribution system - the first point of the switchgear lineup |
|
Feeder / Outgoing Cabinet |
Distributes power to downstream loads; positioned at the end of the cabinet lineup |
|
Bus-tie Cabinet |
Dual-power switching or bus-section tie-in, improving supply reliability |
|
PT Cabinet (Voltage Metering) |
Voltage measurement, can be combined with reactive power compensation |
|
Metering Cabinet |
Dedicated to energy metering circuits |
|
Isolation Cabinet |
Electrically isolates adjacent cabinet groups |
|
Capacitor Cabinet |
Houses high-voltage capacitors for reactive power compensation |
|
Transformer (Auxiliary) Cabinet |
Houses the station service / auxiliary transformer |
These roles can be configured individually or combined (e.g. "Incoming + Bus-tie", "Bus-tie + Feeder + Standby") - see the scheme library and combination examples below.
Step 2 – Determine Current Rating Based on Transformer Capacity

Rated voltage: 3.6kV / 7.2kV / 12kV. Rated current: 630A up to 3150A. Cabinet width is linked to the busbar current rating: 800mm width for branch busbar current up to 1250A; 1000mm width for 1600A and above (thermal stability 40kA).
The exact current rating and breaking capacity should be confirmed by an engineer based on actual transformer capacity and load calculations. If you can provide your transformer capacity, our engineering team will match the precise cabinet type and current step for you.
Step 2 – Determine Current Rating Based on Transformer Capacity

• Circuit breaker operating mechanism: manual, motor-operated, or spring-stored energy - configurable
• Truck (withdrawable) operation: the breaker truck moves between the service and test positions via a manual crank handle (counter-clockwise to withdraw, clockwise to rack in); a dedicated transfer carriage is used only for moving the truck outside the cabinet
• Current transformers (CT) and voltage transformers (PT): selectable ratios, customer-specified ratios supported
• Five-anti ("five-prevention") interlocking system: prevents mis-operation of the breaker, prevents racking the truck in/out on load, prevents closing onto an earthed circuit, prevents energizing with the earthing switch closed, and prevents unauthorized access to a live compartment
Step 4 – Review Reference Schemes Under the Matching Category
Each cabinet role has multiple standard circuit schemes available - see the categorized library below, or consult the full scheme library for the complete set.
2. Circuit Scheme Library by Function
The KYN28A-12(Z) series includes 80 standard main-circuit schemes. Key components include the vacuum circuit breaker (ZN63A / VD4), current transformers, voltage transformers, earthing switches and fuses, with quantities configured per scheme. Cabinet width is 800mm, or 1000mm where rated current is 1600A and above; some overhead-line and metering schemes use a 1660mm cabinet depth.

Category 1: Incoming Cabinet
Brings power into the distribution system via overhead or cable incoming lines. Can be configured standalone, or combined with bus-tie functions for dual-power supply. Typically fitted with circuit breakers, current transformers and, where required, voltage transformers for metering.



Scheme 01–06, 19–28, 33–40 | Single / Dual Incoming Supply, with optional PT | Width 800–1000mm, Depth 1500–1660mm | For single- or dual-source power entry, overhead or cable
Category 2: Feeder / Outgoing Cabinet
Distributes power to downstream loads via overhead or cable outgoing lines, optionally combined with voltage metering (PT) or power factor correction.


Scheme 02, 03, 05, 29–32 | Outgoing Feeder, with optional PT | Width 800–1000mm, Depth 1500mm | For distributing power to downstream loads with cable or overhead outgoing lines
Category 3: Bus-tie Cabinet
Used for bus-section tie-in or dual-power switching. Can be configured standalone, or combined with feeder functions for improved system reliability.


Scheme 07–18, 49–52 | Bus-tie (left/right) / Bus Coupler | Width 800–1000mm, Depth 1500mm | For basic bus-section/dual-power switching
Category 4: PT (Voltage Metering) Cabinet
Dedicated to voltage measurement, optionally combined with surge arresters or bus-tie functions.


Scheme 41–48 | Voltage Metering, with optional Arrester / Bus-tie | Width 800–1000mm, Depth 1500mm | For accurate voltage measurement and protection
Category 5: Metering Cabinet
Dedicated energy-metering circuits, optionally combined with left/right bus-tie or cable incoming.




Scheme 61–76 | Metering, with optional Bus-tie / Cable Incoming | Width 800–1000mm, Depth 1500–1660mm | For accurate energy metering integrated with adjacent cabinet functions
Category 6: Isolation Cabinet
Provides electrical isolation between cabinet groups, optionally combined with bus-tie or voltage metering.


Scheme 53–60 | Isolation, with optional Bus-tie / Voltage Metering | Width 800–1000mm, Depth 1500mm | For sectional isolation between cabinet groups
Category 7: Capacitor & Auxiliary Transformer Cabinet
High-voltage capacitor banks for reactive power (power factor) compensation, and a dedicated cabinet for the station-service (auxiliary) transformer.

Scheme 77 | High-Voltage Capacitor Bank | Width 800–1000mm | Power factor correction
Scheme 78 | Auxiliary/Station-Service Transformer | Width 800–1000mm, Depth 1660mm when transformer capacity exceeds 50kVA | Houses the switchgear's own auxiliary transformer
The schemes above are representative examples. The full KYN28A-12(Z) series includes 80 standard circuit schemes, plus typical multi-cabinet combination examples (e.g. dual-bus incoming + bus-tie + metering + feeder). View Full Scheme Library →
Technical Parameters
|
Item |
Unit |
Data |
|
Rated voltage |
kV |
3.6, 7.2, 12 |
|
Rated frequency |
Hz |
50 |
|
Rated current of circuit breaker |
A |
630, 1250, 1600, 2000, 2500, 3150 |
|
Rated current of switchgear |
A |
630, 1250, 1600, 2000, 2500, 3150 |
|
Rated short-time withstand current (4s) |
kA |
16, 20, 25, 31.5, 40 |
|
Rated peak withstand current |
kA |
40, 50, 63, 80, 100 |
|
Rated short-circuit breaking current |
kA |
16, 20, 25, 31.5, 40 |
|
Rated short-circuit making current (peak) |
kA |
40, 50, 63, 80, 100 |
|
1min power-frequency withstand voltage - phase-phase/earth |
kV |
24, 32, 42 |
|
1min power-frequency withstand voltage - across isolating distance |
kV |
24, 32, 48 |
|
Rated lightning impulse withstand voltage (peak) - phase-phase/earth |
kV |
40, 60, 75 |
|
Rated lightning impulse withstand voltage (peak) - across isolating distance |
kV |
46, 70, 85 |
|
Degree of protection |
- |
IP4X for the enclosure; IP2X when compartment/breaker doors are open |
Operating Conditions
Ambient air temperature: -15°C to +40°C, 24-hour average not exceeding +35°C
• Altitude: ≤1000m for 10kV systems; ≤3000m for 6kV systems
• Relative humidity: daily average ≤95% (daily average water vapor pressure ≤2.2kPa); monthly average ≤90% (monthly average water vapor pressure ≤1.8kPa)
• Seismic intensity ≤ 8 degrees
• Ambient air free from significant pollution by corrosive gases, flammable gases, water vapor or salt fog
• No severe pollution or frequent, intense vibration
Note: if site conditions exceed the above specifications, please consult GangHeng's engineering team.

Structural Features
1. Modular, fully metal-clad construction - assembled from a modular metal-clad frame for consistent quality and easy expansion.
2. High-precision cabinet frame - made from imported aluminum-zinc coated steel sheet, CNC-machined with advanced multi-fold bending and joined with riveted nuts and high-strength bolts; corrosion resistant, lightweight, high strength, strong interchangeability.

3. Compatible circuit breakers - fits GangHeng's own ZN63A-12 (VS1) series or imported VD4 series vacuum circuit breakers; wide applicability, high reliability, maintenance-free.
4. Dedicated service/test positions - the breaker truck has clearly indicated service and test positions for safe, reliable operation.
Full truck interchangeability - trucks of the same rating can be freely swapped between cabinets.

5. Dedicated transfer carriage - moves the truck between cabinets for light, flexible handling.
6. High cable capacity - cable compartment accommodates up to 9 single-core cables.
7. "Five-anti" interlocking - reliable mechanical and electrical interlocks fully satisfy five-prevention (five-anti) safety requirements.
8. Pressure-relief protection - pressure-relief channels in the high-voltage compartments protect personnel safety.

9. Front viewing windows - allow observation of internal component status without opening the door.
10. Front-access maintenance - serviceable from the front, suitable for wall-mounted installation.
11. Insulated compartment barriers - fitted with live-status indication devices between compartments.
12. Custom enclosure finish - polyester powder coating, standard color grey; custom colors available on request (color sample required).

KYN28A switchgear structural diagram: A Busbar compartment B Breaker truck compartment C Cable compartment D
Relay/instrument compartment:
1 Pressure relief device 2 Enclosure 3 Branch busbar 4 Busbar bushing 5 Main busbar 6 Static contact assembly 7 Static contact box
8 Current transformer 9 Earthing switch 10 Cable 11 Surge arrester 12 Earthing busbar 13 Removable partition 14 Shutter (partition)
15 Secondary plug 16 Breaker truck 17 Heater/dehumidifier 18 Withdrawable partition 19 Earthing switch operating mechanism
20 Control wiring duct 21 Base frame
Overall & Installation Dimensions
|
Item |
Configuration |
Value |
|
Height C (mm) |
- |
2300 |
|
Width A (mm) |
Branch busbar rated current up to 1250A |
800 |
|
Width A (mm) |
Branch busbar rated current 1600A and above, 40kA thermal stability |
1000 |
|
Depth B (mm) |
Cable incoming/outgoing |
1500 |
|
Depth B (mm) |
Overhead incoming/outgoing |
1660 |
|
Weight (kg) |
- |
700–1200 |

Installation Base Dimensions
|
Cabinet Width A |
Cabinet Depth B |
L1 |
L2 |
L3 |
|
800 |
1500 (cable) |
800 |
530 |
630 |
|
800 |
1660 (overhead) |
800 |
530 |
630 |
|
1000 |
1500 (cable) |
1000 |
730 |
830 |
|
1000 |
1660 (overhead) |
1000 |
730 |
830 |

Custom Circuit Scheme Configuration
Beyond the standard scheme library, GangHeng offers custom KYN28A-12(Z) configurations, including: widened cabinets, special busbar arrangements, and special secondary circuits.

Path A – With Technical Parameters
Customer provides transformer capacity, system drawings and other parameters; GangHeng's engineering team delivers a custom scheme directly.
Path B – Without Technical Parameters
Customer provides site information, on-site equipment power ratings, and the desired functional outcome; GangHeng's engineering team derives and delivers a custom scheme accordingly.

Notes:
• Custom configurations are priced the same as standard schemes; final cost may vary depending on the specific customization
• Cabinet dimensions may be widened depending on the specific configuration
• No minimum order quantity
• Standard lead time is approximately 30 working days for typical orders; larger or highly customized orders are scheduled case by case
• GangHeng brings 23 years of industry experience, is a qualified supplier for State Grid and China Southern Power Grid, and holds ISO9001 and CCC certifications
Ordering Information
When placing an order, customers should provide:
- Main circuit scheme number, main circuit system diagram, cabinet arrangement drawing, and layout plan
- Auxiliary/control circuit wiring diagram and terminal block layout
- Model, specification and quantity of in-cabinet components
- Where busbar bridges are required (between cabinet rows or through walls), please provide span and ground clearance dimensions
- Enclosure color (standard color is grey unless otherwise specified)
- Any special site conditions or other requirements outside standard operating conditions

If this technical documentation is not available, please refer to Custom Path B above - GangHeng's engineering team will assist in developing the scheme.
Frequently Asked Questions
Q: What are incoming, feeder, bus-tie, PT, metering, isolation and capacitor cabinets used for?
A: Incoming cabinets bring power (utility or transformer) into the distribution system. Feeder cabinets distribute power downstream. Bus-tie cabinets handle dual-power switching or bus-sectioning. PT cabinets measure voltage, metering cabinets measure energy consumption, isolation cabinets separate cabinet groups electrically, and capacitor cabinets provide reactive power compensation. All can be used standalone or combined.
Q: How do I know which current/breaking-capacity rating to choose?
A: This depends on your actual site conditions - transformer capacity, load calculation and system short-circuit capacity. We recommend providing your transformer capacity so our engineers can confirm the exact match.
Q: What is the difference between KYN28 and other high-voltage switchgear types such as KYN61 or the XGN series?
A: KYN28 is rated at 10kV (12kV class) and uses a withdrawable (truck-type) construction. KYN61 is rated at 35kV. KYN61 and the XGN series are typically fixed-mounted designs (the circuit breaker is permanently installed). A withdrawable design is more advanced and safer, with a clearer, more positive isolating break than a fixed-mounted breaker.
Q: What are the advantages of withdrawable (truck-type) switchgear compared with fixed-mounted types?
A: In a fixed-mounted design the breaker cannot be removed, so maintenance carries higher exposure risk. With KYN28's withdrawable truck, the breaker can be racked out completely to the test/maintenance position, giving a more thorough and visible isolation and a higher level of safety.
Q: Is SF6-free / environmentally friendly configuration supported?
A: Yes.
Q: Do you provide installation and commissioning support?
A: Yes - remote video-guided installation support is available, in addition to 24/7 on-site support.
Q: Does a custom scheme cost more or take longer?
A: Pricing depends on the specific customization requested. Standard lead time is approximately 30 working days; larger or highly customized orders are scheduled case by case.
Q: Is there a minimum order quantity (MOQ)?
A: No minimum order quantity - a single unit can be supplied.
Q: Where can I see all 80 standard schemes?
A: Click "View Full Scheme Library" on this page, or contact our engineering team, to access the complete KYN28A-12(Z) main circuit scheme manual with all standard scheme numbers and configuration details.
Request a Technical Proposal
Please provide the following information, and GangHeng's engineering team will match or customize a KYN28A-12(Z) circuit scheme for you:
If technical parameters are available:
- Transformer capacity
- System voltage level